Instrumentation · Beginner

Instrumentation Fundamentals

Pressure, temperature, flow and level measurement, transmitters and switches, 4-20 mA and HART, calibration and signal troubleshooting.

5h 20m5 lessonsFree preview

What you will learn

Select and verify measurement principles; wire and diagnose 4-20 mA loops; use HART; calibrate transmitters and RTD/thermocouple inputs.

Course syllabus

  1. 1. Measurement principles

    Pressure and level · Temperature and flow

  2. 2. Signals

    4-20 mA loops and HART

  3. 3. Calibration

    Calibration and documentation

  4. 4. Troubleshooting

    Signal troubleshooting method

Free lesson · 18m

Pressure and level

Pressure measurement covers gauge, absolute and differential. The distinction matters: a gauge transmitter referenced to atmosphere reads differently from an absolute transmitter, and using the wrong type produces a consistent offset that looks like a calibration error.

Hydrostatic level measurement uses differential pressure and depends on the density of the fluid. If the actual density differs from the design density, the level reading is wrong even though the transmitter is perfectly calibrated. This is one of the most common apparent instrument faults that is actually a process condition.

For closed vessels, wet and dry leg arrangements change the calculation. Always read the installation detail before concluding a level transmitter is faulty.

Key points

Gauge, absolute and differential are not interchangeable; hydrostatic level depends on density; wet and dry legs change the calculation.